跳到内容
CableSimPro文档

半空间线热源交叉校核(英文)

This increment adds cablesim.line-source-crosscheck@0.1.0 without changing the existing buried or electrothermal release bytes. It is a validation-category plugin that consumes the newest successful, current-revision cablesim.buried-reference@0.1.0 job. The v0.1 UI has no arbitrary job/file selector; the exact chosen job ID is sealed in the result. It does not accept arbitrary files, another project, a stale source snapshot or an electrothermal/ampacity job.

Independent equation family

For three line sources at (x_j, y_j) in homogeneous semi-infinite soil with an isothermal ground plane at y=0, the method-of-images coefficient from source j to cable i is

G_ij = rho_soil/(2*pi) * ln(r_image / r_real).

r_image = sqrt((x_i-x_j)^2 + (y_i+y_j)^2). For different cables, r_real is their center distance; for the self term, it is the cable jacket outer radius. Each cable's own center-to-jacket rise adds

R_internal = 1/(4*pi*k_conductor) + sum[ln(r_o/r_i)/(2*pi*k_layer)]

through the five outer material layers. The analytical conductor-center temperature is therefore

T_i = T_ambient + q_i*R_internal + sum_j(G_ij*q_j).

This calculation shares the saved dimensions, material constants, positions, soil thermal resistivity and explicit W/m sources, but it does not share the FEM weak form, sparse assembly or solution. It is consequently useful as an independent equation-family check, not as experimental validation.

Why a difference is expected

The FEM source job uses a finite rectangle with ambient-temperature ground, side and bottom boundaries and polygonal interfaces. The analytical model has only an isothermal ground plane and an otherwise infinite soil half-space, and represents each cable externally as a line source. Its internal cable resistance remains a circular six-layer solution. Reported FEM-minus-analytical differences therefore combine at least:

  • finite side/bottom truncation in the FEM domain;
  • line-source and circular-interface approximations in the analytical reference;
  • polygonal geometry and P1 mesh discretization;
  • numerical rounding and source integration.

There is deliberately no built-in pass/fail tolerance. Expanding the FEM soil box should normally reduce artificial cooling if truncation dominates, but a decreasing difference does not prove infinite-domain accuracy, mesh independence, material accuracy or compliance.

Provenance and fail-closed behavior

The host copies only the source job's sealed thermal.json and a bounded metadata record containing its exact plugin pin, command, arguments, project revision and snapshot digest. The worker recalculates the comparison from the current saved Scenario and CircularRecipe. It rejects changed powers, domain scale, resolution, ambient temperature, soil conductivity, geometry, plugin identity or source command. The resulting line-source.json is hashed like every other project artifact.

The UI shows phase-by-phase source heat, FEM peak, analytical center temperature, difference, the external resistance matrix and the finite-domain dimensions. It never promotes the report to the host ampacity result and labels the absence of an engineering acceptance threshold.

Evidence gate

Line-source cross-check evidence runs:

  • the full host regression suite and checked-in schema/integrity checks;
  • real Gmsh/scikit-fem buried sources at domain scales 4, 8 and 16 on Linux and Windows, checking that this fixture approaches the unchanged half-space result;
  • the actual install/enable/source/invoke/download chain, cross-project and stale source rejection, and no engineering revision change.

The default synthetic fixture is not manufacturer data or a published cable rating. Exact numerical claims must cite an exact commit and its workflow artifacts.


本页由仓库文件 docs/plugins/LINE_SOURCE_CROSSCHECK.md 生成,修改请编辑该文件。